VLT® Line reactor MCC 103 - line reactor for load sharingMCC 103 line reactor is specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive in applications using load sharing. Use the MCC 103 line reactor for up to 500V mains supply with 50 Hz or 60 Hz mains frequency. The MCC 103 line reactor is available with IP00 enclosure protection.Specifications:,,Rated voltage:,,380-500 VRated frequency: 50-60 HzRated current,,72 AInductance L: 102 uHWinding resistance: 2.6 mOhmL tolerance: ±10%Mains connection - type: Screw terminalMains connection - dimension: 35 mm2Mains connection - tightening torque: 4.0-5.0 NmPE connection - type: Screw connectionPE connection - dimension: M5x10Ambient temperature without derating: -10 to +45 C°Derating > 45 °C: 2.5%/KDerating > 1km: 5%/1kmType of cooling: Cooled by natural convectionOperating conditions: Permanent operation with 100% loadWeight: 5.95 kgDimensions - HxWxD: 195x155 x110 mmEnclosure degree: IP00Mounting,,: Vertical or horizontal