VLT® Line reactor MCC 103 - line reactor for load sharingMCC 103 line reactor is specially designed to match the Danfossfrequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVACDrive in applications using load sharing. Use the MCC 103 line reactorfor up to 500V mains supply with 50 Hz or 60 Hz mains frequency. The MCC103 line reactor is available with IP00 enclosure protection.Specifications:Rated voltage: 380-500 VRated frequency: 50-60 HzRated current 145 AInductance L: 51 uHWinding resistance: 1.0 mOhmL tolerance: ±10%Mains connection - type: Bus-barMains connection - dimension: 1 x Ø7.1Mains connection - tightening torque: - NmPE connection - type: Bolt connectionPE connection - dimension: M5Ambient temperature without derating: -10 to +45 C°Derating > 45 °C: 2.5%/KDerating > 1km: 5%/1kmType of cooling: Cooled by natural convectionOperating conditions: Permanent operation with 100% loadWeight: 8.25 kgDimensions - HxWxD: 160x185 x135 mmEnclosure degree: IP00Mounting : Vertical or horizontal